irshad, kashif and Habib, Khairul and basrawi, firdaus and Nagarajan, T and saidur, R and Saha, Bidyut B. (2015) Thermal comfort study of a building equipped with thermoelectric air duct system for tropical climate. Applied Thermal Engineering, 91. pp. 1141-1155. ISSN 13594311
Habib ATE.pdf
Download (2MB)
Abstract
This paper examined the performance of a thermo-electric air duct system (TE-AD), which employs the thermo-electric module (TEMs) inside an air duct for providing thermal comfort in Malaysian environment. Twenty human subjects were exposed to test room equipped with TE-AD system operating at six different input current supply from 2 A to 7 A. Both objective and subjective measurements were carried
out. Results show that with the increment of input current supply to the TE-AD system, subject's thermal response related to indoor condition of test room shifted fromwarm to neutral. Optimum performance of the TE-AD system was obtained at the input current supply of 6 A, more than 80% of subjects responded in the range of ±1 and meets ASHARE standards of acceptability criteria. Further increase in input current supply deteriorates the cooling performance of the TE-AD system. Economic comparison of the TE-AD
system with the existing air conditioning system shows that economic saving of US$ 127.34/year can be achieved with additional benefits of Freon free, convenient installation, no moving part and reliable operation.
Item Type: | Article |
---|---|
Impact Factor: | 2.739 |
Subjects: | T Technology > TJ Mechanical engineering and machinery |
Departments / MOR / COE: | Departments > Mechanical Engineering Research Institutes > Energy |
Depositing User: | Unnamed user with email khairul.habib@petronas.com.my |
Date Deposited: | 07 Oct 2016 01:42 |
Last Modified: | 07 Oct 2016 01:42 |
URI: | http://scholars.utp.edu.my/id/eprint/11760 |