Study on two stage activated carbon/HFC-1340 based adsorption chiller

Habib, Khairul and Abd Majid, Mohd Amin and Sulaiman, S. A. (2013) Study on two stage activated carbon/HFC-1340 based adsorption chiller. [Citation Index Journal]

[thumbnail of 3930_001.pdf]
Preview
PDF
3930_001.pdf

Download (283kB) | Preview

Abstract

In this paper, a theoritical analysis of a thermally driven two-stage four-bed adsorption chiller utilizing low-grade waste heat of temperatures between 50 deg C and 70 deg C in combination with a heat sink (cooling water) of 30 deg C for air-conditioning application has been described. Activated carbon (AC) of type Maxsorb III/HFC-134a pair has been examined as an adsorbent/refrigerant pair. FORTRAN simulation program is developed to analyse the influence of operating conditions (hot and cooling water temperatures and adsorption/desorption cycle times) on the cycle performance in terms of cooling capacity and COP.The main advantage of this two-stage chiller is that it can be operational with similar regenerating temperature lifts than other heat-driven single-stage chillers. Simulation results show that the two-stage chiller can be operated effectively with heat sources of 50 deg C and 70 deg C in combination with a coolant at 30 deg C.

Item Type: Citation Index Journal
Depositing User: AP Ir Dr Mohd Amin Abd Majid
Date Deposited: 28 Apr 2015 02:54
Last Modified: 28 Apr 2015 02:54
URI: http://scholars.utp.edu.my/id/eprint/11639